Valve Alarm Combo Unit
Valve Alarm Combo Unit

With this product’s highly innovative 2 in 1 design, we have combined our first-class Area Alarm with our Valve Box, acommodating both in one space providing an aesthetically pleasant, affordable package. The ability to install sensors directly inside the Valve Box eliminates the need for prolonged, complex maintenance, as well as the search for absent sensors. Amico’s Valve Alarm Combination Unit is built to offer users years of proficient service. Previous concerns regarding convenience, space, maintenance and accessibility become uncertainties of the past, with the ground-breaking, Valve Alarm Combo Unit.

DOWNLOADS:
BROCHUREMANUALSSPEC SHEETSDRAWINGS

Valve Alarm Combo Unit Drawings

FilenameSizeType
ape_dr_alarm_valve_combo0.15MBDWG
ape_dr_alarm_valve_combo2.9MBRVT
ape_dr_alarm_valve_combo0.06MBPDF

General Features

  • 2 in 1 design combines the Area Alarm and Zone Valve Box to compensate for space restrictions
  • True digital, illuminated LED display is readable even in poor lighting conditions
  • High/low alarm set-points are field adjustable for each gas service
  • Repeat alarm is adjustable from 1 to 60 minutes or off
  • Gas-specific sensor with DISS nut and nipple
  • Alarm buzzer in excess of 90 decibels
  • Each module is marked with an approved medical gas identification label
  • Pre-mounted pull-out ring allows for ease of maintenance
  • Individual microprocessor for each display and sensor module; digital sensor is mounted locally
  • Dry contacts for remote monitoring of the high and low alarm

Model Numbers:

 

AVCLN-XXGXXGXXGXXGXXGXXG



The Letter “L” Defines the Language

U = English (NFPA)

E = English (CSA/ISO)

F = French (CSA/ISO)

S = Spanish (NFPA)

 

The ”N” Defines the # of Valves:

1 = 1 Valves

2 = 2 Valves

3 = 3 Valves

4 = 4 Valves

5 = 5 Valves

6 = 6 Valves

 

The ”G” Defines the Gas:

O = Oxygen

A = Medical Air

V = MedVac

2 = Nitrous Oxide

N = Nitrogen

C = Carbon Dioxide

W = WAGD (NFPA)

E = AGSS (ISO)

I = Instrument Air

 

Replace ”XX” with the Required Valve Size:

05 = 1/2" [1.3 cm]

07 = 3/4" [1.9 cm]

10 = 1" [2.5 cm]

12 = 1-1/4" [3.2 cm]

15 = 1-1/2" [3.8 cm]

20F = 2" [5.1 cm]

 

NOTE:

The power supply will require 1 gang per box.

 

Example: English, 3 valves, 1/2" [1.3 cm] oxygen, 3/4" [1.9 cm] medical air and 1-1/4" [3.18 cm] medvac. Will be in a 4 gang box.

AVCU3-05O07A12V

The 1-1/2" [3.8 cm] valve will have an empty space above the valve.

Example: A box with a 1/2" [1.3 cm] oxygen, 3/4" [1.9 cm] medical air and a 1-1/2" [3.8 cm] medvac valves will require a 5 hole box not a 3 hole box.

 

The 2" [5.1 cm] valve will be assembled in a 6-1/2" [16.5 cm] deep box and shall accommodate up to a maximum of 4 gases. The 2" [5.1 cm] valve shall be positioned on the bottom of the assembly. Refer to 2" [5.1 cm] Valve Drawing provided on page 2.

 

The height measurements of the 6-1/2" [16.5 cm] valve box are the same as the 3-7/8" [9.84 cm] valve box. When comparing height measurements, consider the gap above the 2" [5.1 cm] valve.

 

Example: A valve box with 2" [5.1 cm], 1/2" [1.3 cm] and a power supply would be in a 3 gang 6-1/2" [16.5 cm] deep box, which would be the same height as the 4 gang 3-7/8" [9.84 cm] box.