Economy Manifold
Economy Manifold
The Amico Economy Manifold incorporates the basic necessities for distribution and monitoring of gas throughout a facility. 
 
The Manifold is semi-automatic and shall switch from “In Use” bank to “Reserve” bank once the “In Use” bank depletes. Manual operation shall be required at the time of changing cylinders to ensure that the “Reserve” bank is changed to “In Use”. The bank that has new cylinder(s) shall be the “Reserve”.
 
A pressure switch controls the remote alarm which indicates the “In Use” to “Reserve” supply switch-over and that cylinder replacement is necessary. The pressure switch is set to trigger an alarm condition when the operating bank pressure drops pressure slightly above the secondary bank outlet pressure and just before the bank switch-over occurs.
 
All Manifold regulators, piping and control switching equipment shall be cleaned for oxygen service.
 
FLOW CAPACITY
Oxygen, Nitrous Oxide, Medical Air, Carbon Dioxide: 4500 SCFH (2,123 L/min)
Nitrogen: 6000 SCFH (2,831 L/min)
DOWNLOADS:
BROCHUREMANUALSSPEC SHEETS

Economy Manifold Specs

FilenameSizeType
ape_sp_eco_mani0.57MBPDF
ape_as_sp0.72MBPDF

General Features

  • Heavy duty line regulator to produce optimum gas flow
  • Pressure switch with dry contacts to indicate “Reserve” in use alarm
  • Removable cabinet enclosure for easy installation and service
  • Maximum inlet pressure is 3,000 psi (20,685 kPa)
  • Maximum delivery pressure is 180 psi (1,242 kPa)

Model Numbers:

M3EC-S-HH-L-GAS (Manifold Cabinet)


EC = Economy

S = Single Heavy Duty Line Regulator

HH = High Pressure

 

The Letter “L” Defines the Language

U = English (NFPA)

S = Spanish (NFPA)

 

The “GAS” Defines the Type of Gas:

Oxygen = OXY

Nitrogen = NIT

Medical Air = AIR

Carbon Dioxide = CO2

Nitrous Oxide = N2O

 


 

M2-HBYY-XXL-GAS (Header-Bar Assembly)


 

“YY” Defines the Type of Header-Bar Assembly:

TS = Straight c/w Stainless Pigtails

TC = Straight c/w Copper Pigtails

XS = Staggered c/w Stainless Pigtails

XC = Staggered c/w Copper Pigtails

 

“XX” Defines the Number of Cylinders:

04 = 2 x 2

08 = 4 x 4

 

The Letter “L” Defines the Language

U = English (NFPA)

S = Spanish (NFPA)

 

The “GAS” Defines the Type of Gas:

Oxygen = OXY

Nitrogen = NIT

Medical Air = AIR

Carbon Dioxide = CO2

Nitrous Oxide = N2O

 

Wall Bracket for Header-Bar Assembly: M-X-HB-WLBRKIT

 

Note:

For Oxygen service, use only copper pigtails.

Languages

  • English