DRY ROTARY VANE PUMPS
DUPLEX STACK MOUNTED VACUUM SYSTEMS
Furnish and install, where shown on the drawings a prefabricated duplex stack mounted dry rotary vane vacuum system model____________ as manufactured by:
Amico Source
Toll Free Tel: 1.877.462.6426
The unit furnished shall be a standard
catalog item of the supplier regularly engaged in the business of providing
packaged systems for hospitals and laboratories and shall meet and exceed the
requirements of NFPA 99.
The package shall include two oil-less
rotary vane vacuum pumps and associated equipment, one vertical ASME tank and
one duplex control panel. The only field connections required will be system
intake, exhaust and power connection at the control panel. All components shall
be completely pre-piped and pre-wired to single-point service connections. All
interconnecting piping and wiring shall be completed and operationally tested
prior to shipment. Provide liquid tight conduit, fittings and junction boxes for
all control and power wiring.
The vacuum pumps shall be of
the oil-less continuous duty rotary vane air-cooled design, equipped with
long life, high performance compound vanes, driven by 40 degree C rise, 3 phase,
60 cycle, ODP, NEMA C-Face, design B induction type motors.
Each vacuum pump shall be driven by a ____
HP, 3 phase, 60 cycle, ______ volt, 1750 RPM, TEFC NEMA C-face, foot mounted
motor. Each pump shall have a capacity of ____SCFM at 19 “HG.
The system shall include the following
accessories for each pump: inlet check valve, inlet isolation valve, vacuum
control switch, integral inlet filter, exhaust muffler and vacuum relief valve.
Provide flexible connectors on inlet and exhaust of each pump, exhaust tee with
union, drip-leg with cock valve as well as copper tubing with shut-off cock for
gauge and vacuum switches. The system shall include a _______ gallon vacuum
storage tank of ASME construction.
The tank shall be rated for full vacuum service and shall be equipped with a
valved by-pass, vacuum gauge and manual tank drain. The inside of the tank shall
be coated for rust protection with a two component coating which provides a
hard, durable lining.
Provide vibration mounting per NFPA 99.
The system shall include a UL listed control
panel in a NEMA 12 enclosure with the following accessories for each
pump:
Externally operable circuit breaker with
door interlock, control circuit transformer with fused primary and secondary
coils, H-O-A switch, magnetic starter with 3 leg overload protection, hour
meter, motor running light and
minimum run timer to prevent short cycle operation. Provide the panel with a
multiple position selector switch for selection of normal operation (automatic
alternation) or manual selection of lead and lag pumps if one of the pumps is
taken out of service due to scheduled maintenance. Provide audible and visual
local alarm (complete with indicating lights and individual sets of auxiliary
contacts wired to the terminal strip for remote alarm indication) for reserve
vacuum pump in use. All control and alarm functions shall remain energized while
any vacuum pump in the system remains electrically on-line. The lag vacuum pump
shall be able to start automatically if the lead vacuum pump fails to operate.
The vacuum system shall be guaranteed in
writing by the manufacturer for a period of 12 months from the date of start-up
or 18 months from the date of shipment (whichever comes first) against defects
in design, materials, or construction.
The service of a factory trained
representative shall be made available at the jobsite to check installation,
start-up and instruct operating personnel in the proper operation and
maintenance.